Trident Modular Temporary Power Restoration System (10kVA / 20kVA)

Trident is the 45 lb one-person service saver for meters a wheeled unit cannot reach. Each 10 kVA module restores a missing hot or missing neutral on 120/240V or 120/208V service – one module for 100A, two for 200A. Control unit 9 lbs.

Trident Modular Temporary Power Restoration System
45 lb one-person service saver for hard-to-reach meters

Trident is a modular service saver (add-a-phase autotransformer) that restores a missing hot leg or missing neutral on single-phase 120/240V or 120/208V service. It is built for meters a wheeled cart cannot reach. Each hermetically sealed 10 kVA autotransformer weighs 45 lbs. The control unit weighs 9 lbs. A single troubleman or lineman can carry the system up stairs, down an alley, or across a finished yard, connect it at the meter, and restore service in minutes. One module covers 100A. Two restore up to 200A. Designed, wound, and assembled in Shelton, Connecticut.

What Trident restores

  • Open hot leg, using one good hot and a good neutral
  • Open neutral, using two good hot legs
  • Not both on the same service
  • Not 3-phase

Key advantages

  • One-person carry: 45 lb modules + 9 lb control unit. Fits a light truck or car trunk.
  • Redundant protection: 50A breaker on each module, plus voltage and current monitoring. If one module is installed and the load exceeds what it can carry, Trident shuts off and protects the transformer and the home.
  • Sealed, flame-rated, weatherproof: Hermetically sealed toroidal autotransformers in non-metallic flame-rated ABS. Built to sit outdoors in wet conditions. No driven ground rod.
  • Meter-base install: Single-turn universal adapter for ring-type and ringless sockets. Neutral included. No temporary overhead conductors.
  • Sized to the ticket: One 10 kVA module for 100A. Two modules for 200A. Components sold separately.
  • Made in USA: Shelton, CT. Typical lead time 1–2 weeks. 3-year warranty.

Specifications

Specification Details
Model TRIDENT 10/20kVA Service Saver
Rating 10 kVA (one autotransformer) / 20 kVA (two autotransformers)
Recommended service 100A / 200A
Breaker 2 × 50A (one per autotransformer)
Autotransformer weight 45 lbs each
Control unit weight 9 lbs
Total two-module set Two 45 lb transformers + 9 lb control unit
Enclosure Hermetically sealed, flame-rated non-metallic ABS
Grounding No driven ground rod required
Connection Single-turn meter adapter, 200A (AM, AG, or CL320)
Versions A, B, or C (C flexible gooseneck most common)
Service type 120/240V or 120/208V, single-phase, 3-wire
Protection Per-module 50A breaker + volt/amp monitoring
Origin Shelton, Connecticut, USA
Lead time 1–2 weeks
Warranty 3 years

When to use Trident
Use Trident when the meter is up stairs, behind a gate, down an alley, across a finished yard, on an easement, or on ground a cart cannot cross. It is the service saver for troublemen and single-person first response on 100A and 200A residential tickets.

How it connects
Remove the meter. Land the adapter in the socket. Lock it with the single-turn screw. Set the meter back on the adapter. Plug in one module or two. Follow the breaker sequence. Confirm 120V hot-to-neutral and 240V hot-to-hot. Leave the unit on-site until the underground repair is scheduled.

Need a 45 lb / 9 lb carry-in service saver?
Call (203) 954-0050 or request a quote. We will spec Version A, B, or C to the sockets and trucks you run.

Weight 110 lbs

Reviews

There are no reviews yet.

Be the first to review “Trident Modular Temporary Power Restoration System (10kVA / 20kVA)”

Your email address will not be published. Required fields are marked *

Shopping Cart
Products
Toroidal transformers & magnetics — made in Shelton, CT since 1982
Made in USA  ·  Intertek (ETL) Certified  ·  UL Recognized

Product Inquiry Form