Snowstorm Temporary Power Restoration With a 45 lb Autotransformer

Snowstorm temporary power restoration is difficult when the only tools on the truck are 150 lb wheeled service savers. Ice, snow, and finished yards stop a cart before it reaches the meter. A 45 lb modular autotransformer gets one troubleman to the socket, restores the missing hot leg, and keeps the customer online until the permanent dig can be scheduled.

The January Call

A residential service lost one hot leg after a snowstorm. The remaining hot and the neutral were still good. Half the 120V circuits and all 240V loads were out. The driveway and side yard were covered in ice. A traditional wheeled service saver (the class often called a Servisavor or Restore-Lite style cart) weighed well over 150 lb. Unloading it and rolling it across the slick surface would have required two people and still risked a fall or a stuck cart.

The troubleman carried the modular units by hand. One 10 kVA autotransformer and the control unit restored the missing hot leg at the meter. Full 120/240V returned. The underground cable repair was scheduled for the following week when the ground and the weather allowed a proper dig. The customer had power the entire time.

Why Heavy Wheeled Units Fail in Snow

Condition150+ lb wheeled service saver (Servisavor / Restore-Lite class)45 lb modular autotransformer
Ice and snowHard to roll, high tip and slip riskCarried by one person
Stairs, gates, alleysOften cannot reachHand-carried to the meter
Finished yardsCart path damages landscapingNo cart required
Crew sizeFrequently two peopleOne troubleman
One-man lift limitsOften exceeded45 lb per autotransformer

Older and current wheeled service savers were built for open driveways. When the path is ice or a narrow side yard, the cart becomes the limiting factor. Snowstorm temporary power restoration needs a unit that can be carried.

How the Restoration Works (No Generator)

The unit is a temporary power restoration autotransformer. It does not need a generator. It uses the two remaining good conductors on a 120/240V or 120/208V service to regenerate the missing one.

  • Open hot leg: one good hot + good neutral → restores the missing hot
  • Open neutral: two good hots → restores the missing neutral

One 10 kVA module covers a 100A service. Two modules restore up to 200A. Installation uses a meter adapter at the socket. No temporary overhead lines are pulled across the yard.

MethodEquipment neededSnowstorm practicality
GeneratorFuel, noise, exhaust, separate groundingPoor – logistics and placement issues
Temporary overhead linesExtra crew, poles or trees, liabilityPoor – ice, traffic, and yard hazards
Heavy wheeled service saverCart, two people, clear pathLimited on ice
45 lb modular autotransformerExisting good conductors onlyHigh – carried to the meter

Key Features That Matter in Winter

FeatureField benefit
45 lb autotransformersOne-person carry under typical one-man lift rules
Dual-trip protection on each autoIndependent breakers protect each module from overcurrent; thermal protection guards the windings
Hermetically sealed transformersEpoxy-sealed construction keeps moisture and snowmelt out of the windings
Locked connectionsSecure mating so vibration or movement does not loosen field connections
No generator requiredPure autotransformer; uses only the conductors that are still energized
ModularCarry only what the service needs

The dual-trip design means each autotransformer has its own overcurrent protection. A problem on one module does not take the other offline. The hermetic sealing and locked connectors are intended for units that sit outside for days in wet or freezing conditions.

The Week-Later Permanent Repair

Because power was restored immediately, the utility did not dig the cable in the snow. The unit stayed at the meter. A week later the crew returned, removed the modules, completed the permanent splice, and restored the normal secondary. The customer experienced one short outage at the start and normal power for the rest of the week.

TimelineWhat happened
Day 0, snowstormFailed hot leg confirmed. 45 lb modules installed. Power restored.
Days 1–7Unit left on site. Customer has full 120/240V.
Day 7Permanent cable repair completed. Modules removed.

This is the operational value of snowstorm temporary power restoration. The temporary unit buys calendar time so the dig happens in better weather and on normal crew hours.

FAQ

Does this need a generator?
No. It is an autotransformer. It regenerates the missing hot or neutral from the conductors that are still good.

How does it compare with a Servisavor or Restore-Lite in snow?
Those are typically heavier wheeled carts. The modular 45 lb design is carried by one person and reaches meters a cart cannot.

What is dual-trip protection?
Each autotransformer has its own breaker for overcurrent. Thermal protection also guards the windings if the unit stays loaded for an extended period.

Can it stay outside in snow and rain?
The transformers are hermetically sealed and the connections are locked. The system is designed for temporary outdoor use while the permanent repair is completed.

When should a utility choose this over a wheeled unit?
When the meter cannot be reached by a cart: snow, ice, stairs, alleys, gates, or finished yards.

Is this a service saver?
Yes. It is the modular, one-person option in the temporary power restoration line. It is also called an add-a-phase or add-a-leg unit in some regions.

Product Callout

Bridgeport Magnetics Trident
45 lb modular autotransformer for snowstorm temporary power restoration. Restores a missing hot leg or missing neutral at the meter. No generator required. Dual-trip protection on each autotransformer. Hermetically sealed. Designed for one-person deployment in ice, snow, and hard-to-reach locations. Made in Shelton, Connecticut.

Phone: (203) 954-0050
Email: [email protected]
bridgeportmagnetics.com/trident-service-saver/

Shopping Cart
Products
Toroidal transformers & magnetics — made in Shelton, CT since 1982
Made in USA  ·  Intertek (ETL) Certified  ·  UL Recognized

Product Inquiry Form